Lesson 7 of 15 · 25 min
Detailed sizing with worked examples
- Size home, society and factory systems
Home
Critical 1.5 kW × 4 h ÷ 0.81 ≈ 7.4 kWh; PCS 3 kW.
Society
Lifts/pumps 40 kW × 2 h + 60 kWh evening shift → ≈ 175 kWh, 60 kW PCS.
Factory
Shave 450→350 kVA for 1.5 h windows ≈ 150 kWh ÷ 0.81 ≈ 185 kWh, 100 kW PCS; check NPV.
India note
India example: Run all three in the calculator and compare Basic/Recommended/Max.
Key takeaways
- Size by goal
- Take the max of needs
- Optimise on NPV