Basic terms made easy
kW vs kWh, DoD, SoC, C rate and more, explained without jargon.
kW vs kWh
kW is power: how fast energy flows, like the size of a tap. kWh is energy: how much is stored, like the size of the tank. One kWh is one 'unit' on your electricity bill. A 50 kW / 100 kWh battery can give 50 kW for 2 hours.
Capacity: nominal vs usable
Nominal capacity is the label size. Usable capacity is what you can actually use, because a battery should not be fully emptied. 100 kWh nominal at 90% DoD = 90 kWh usable.
DoD and SoC
Depth of Discharge (DoD) is how much of the battery you empty in one cycle. State of Charge (SoC) is how full it is right now, like a phone battery percentage.
C rate
C rate tells how fast a battery charges or discharges compared to its size. 0.5C means it takes 2 hours to fully charge or discharge. 1C means 1 hour.
Round trip efficiency
Some energy is lost going in and out. At 90% efficiency, putting in 100 units gives you back about 90 units.
Cycle life, degradation and warranty
One full charge and discharge is one cycle. Good LFP batteries last 6,000+ cycles, about 15 years at one cycle a day. Capacity slowly reduces (degradation), typically 2–3% a year. A warranty usually guarantees, for example, 70% capacity after 10 years.
Real life example from India
Your society's lift needs 10 kW and you want 3 hours of backup. That is 30 kWh. At 90% DoD and 90% efficiency, you need a battery of about 30 ÷ 0.81 = 37 kWh nominal.
Key takeaways
- kW = speed, kWh = amount
- Usable = nominal × DoD
- LFP lasts ~6,000 cycles with 2–3% fade a year